Three-Phase Isolation Transformer – 50 kVA (Copper Windings, K-Factor 13, Dyn11)

SKU: IT 0050000 - 23 - 000 - CU - 13

50 kVA 3-phase isolation transformer with copper windings, K-Factor 13 design, and Dyn11 vector group. High efficiency (>96%) and available in IP00 (open) or IP23 (enclosed) protection. Ideal for isolating and protecting sensitive loads with significant harmonic content

  • Description
  • Additional information

Description

is a high-performance isolation transformer specifically designed for applications with substantial harmonic distortion. Its copper windings and K-Factor 13 rating effectively mitigate these harmonics, ensuring stable and clean power. The Dyn11 vector group contributes to balanced three-phase operation and minimal leakage reactance. Rated at 50 kVA with an efficiency exceeding 96%, this transformer is suitable for continuous operation up to 50 °C ambient temperature. Choose between the IP00 open construction for well-maintained environments and the IP23 enclosure for added protection against dust and humidity. It complies with IEC 61558-1, IEC 61558-2-4, IEC 60076-1, and IEC 60601-1 standards, guaranteeing galvanic isolation and adherence to strict safety protocols. 🔧 Specifications:
• Rated Input Voltage: 3×400 VAC ±10%
• Rated Output Voltage: 3×400 VAC ±10%
• Rated Power: 50 kVA
• Rated Current: 3×90.9 A
• Insulation Class: H
• Maximum Ambient Temperature: 50 °C
• Efficiency: >96%
• Protection Degree: IP00 (open); IP23 (enclosed)
• Frequency: 50–60 Hz
• K-Factor: 13
• Windings: Copper
• Vector Group: Dyn11
• Dimensions (IP00): 600 × 320 × 600 mm
• Weight (IP00): 345 kg
• Dimensions (IP23): 780 × 570 × 810 mm
• Weight (IP23): 395 kg
• Standards Compliance: IEC 61558-1; IEC 61558-2-4; IEC 60076-1; IEC 60601-1 💡 Applications:
• Isolation for medical devices and laboratory equipment with high harmonic loads
• Protection of sensitive industrial control systems from harmonic distortion
• Galvanic separation in automation panels with non-linear loads
• Power conditioning for electronics and instrumentation sensitive to harmonics

Additional information

referance no

IT 0050000 – 23 – 000 – CU – 13

description

3Ph Isolation Transformer 50KVA-CU -K13 – DYN11

rated input voltage

3*400Vac +- 10%

rated output voltage

3*400Vac +- 10%

rated power

50Kva

Rated Current

3*90.9A

Insulation Class

H

Maximum Ambient Temprature

50C

efficiency

> 96%

Protection degree

IP00 Without Enclosure & IP23 With Enclosure

Frequency

50/60Hz

K- Factor

K13

Windings

Copper

Vector Group

DYn11

Dim of IP00

600*320 *600

Weight of IP00

345kg

Dim of IP23

780*570*810

Weight of IP23

395kg

IEC Standared

IEC 61558-1 ,IEC 61558-2-4,IEC 60076-1,IEC 60601-1