63 kVA 3-phase isolation transformer with copper windings, K-Factor 13 design, and Dyn11 vector group. High efficiency (>96%) and available in IP00 (open) or IP23 (enclosed) protection. Ideal for isolating and protecting sensitive loads with high harmonic content
- Description
- Additional information
Description
is a high-performance isolation transformer specifically designed for applications with significant harmonic distortion. Its copper windings and K-Factor 13 rating effectively mitigate these harmonics, ensuring stable and clean power. The Dyn11 vector group contributes to balanced three-phase operation and minimal leakage reactance. Rated at 63 kVA with an efficiency exceeding 96%, this transformer is suitable for continuous operation up to 50 °C ambient temperature. Choose between the IP00 open construction for well-maintained environments and the IP23 enclosure for added protection against dust and humidity. It complies with IEC 61558-1, IEC 61558-2-4, IEC 60076-1, and IEC 60601-1 standards, guaranteeing galvanic isolation and adherence to strict safety protocols. 🔧 Specifications:
• Rated Input Voltage: 3×400 VAC ±10%
• Rated Output Voltage: 3×400 VAC ±10%
• Rated Power: 63 kVA
• Rated Current: 3×90.9 A
• Insulation Class: H
• Maximum Ambient Temperature: 50 °C
• Efficiency: >96%
• Protection Degree: IP00 (open); IP23 (enclosed)
• Frequency: 50–60 Hz
• K-Factor: 13
• Windings: Copper
• Vector Group: Dyn11
• Dimensions (IP00): 600 × 390 × 500 mm
• Weight (IP00): 410 kg
• Dimensions (IP23): 780 × 570 × 810 mm
• Weight (IP23): 460 kg
• Standards Compliance: IEC 61558-1; IEC 61558-2-4; IEC 60076-1; IEC 60601-1 💡 Applications:
• Isolation for medical devices and laboratory equipment with high harmonic loads
• Protection of sensitive industrial control systems from harmonic distortion
• Galvanic separation in automation panels with non-linear loads
• Power conditioning for electronics and instrumentation sensitive to harmonics
Additional information
referance no | IT 0063000 – 23 – 000 – CU – 13 |
---|---|
description | 3Ph Isolation Transformer 63KVA-CU -K13 – DYN11 |
rated Power | 63KVA |
Rated Current | 3*72.2A |
Insulation Class | H |
Maximum Ambient Temprature | 50C |
Efficiency | >96% |
Protection degree | IP00 Without Enclosure & IP23 With Enclosure |
Frequency | 50/60Hz |
K- Factor | K13 |
Windings | Copper |
Vector Group | DYn11 |
Dim of IP00 | 600*390*500 |
Dim of IP23 | 780*570*810 |
Weight of IP00 | 460KG |
IEC Standared | IEC 61558-1 ,IEC 61558-2-4,IEC 60076-1,IEC 60601-1 |