10 A reactor, 4 % impedance (2.941 mH) for harmonic filtering in 3 × 400 V networks. IP00, Class H.——
- Description
- Additional information
Description
Class H insulation and natural air cooling (AN) ensure reliable operation up to 40 °C. Tested to 4000 V AC per IEC 60076 6 / IEC 60289.
🔧 Specifications:
• Rated Voltage: 3 × 400 V AC
• Short Circuit Voltage (Uk): 4 %
• Rated Current: 10 A
• Inductance: 2.941 mH
• Frequency: 50 Hz
• Protection: IP00
• Inductance Deviation: –10 %
• Insulation Class: H
• Cooling: AN
• Ambient Temp: 40 °C
• Test Voltage: 4000 V AC
• Dimensions: 180 × 100 × 180 mm
• Weight: 4.70 kg
• Standards: IEC 60076 6, IEC 60289
💡 Applications: VFD input reactors, motor harmonic mitigation, automation panels.
Additional information
referance no | LR3-0010-04-000 |
---|---|
description | Three phase line reactor 10A-4% |
rated voltage | 3*400Vac |
short circuit voltage( uk) | 4% |
rated current | 10A |
Inductance | 2.941mh |
Rated Frequency | 50HZ |
Protection degree | IP00 |
inductance deviation | -10.00% |
insulation class | H |
Cooling | AN |
Ambient temprature | 40 C |
Test Voltage | 4000Vac |
dim | 300*178.8*250 |
weight | 25.37kg |
Standared | IEC 60076 -6 , IEC 60289 |