250 A reactor, 0.117 mH, 4 % impedance for heavy duty 400 V drives. IP00, Class H.
- Description
- Additional information
Description
. Natural air cooled, Class H insulation; operates at 40 °C. Tested 4 kV; IEC 60076 6 / 60289 compliant.
🔧 Specifications:
3×400 V AC │ Uk 4 % │ 250 A │ 0.117 mH │ 50 Hz │ IP00 │ –10 % │ Class H │ AN │ 40 °C │ 4000 V AC │ 300×198.8×250 mm │ 33.79 kg │ IEC 60076 6, 60289.
💡 Applications: Large HVAC VFDs, pumping stations, harmonic mitigation
Additional information
referance no | LR3-0250-04-000 |
---|---|
description | Three phase line reactor 250A-4% |
rated voltage | 3*400Vac |
short circuit voltage( uk) | 4% |
rated current | 250A |
Inductance | 0.117mh |
Rated Frequency | 50HZ |
Protection degree | IP00 |
inductance deviation | -10.00% |
insulation class | H |
Cooling | AN |
Ambient temprature | 40 C |
Test Voltage | 4000Vac |
dim | 300*198.8*250 |
weight | 33.79kg |
Standared | IEC 60076 -6 , IEC 60289 |